Why Static Pressure Problems Become More Visible in Heating Season


Steve Roberts • February 17, 2026
0 minute read
Share
static pressure problems

Tenant complaints about cold spots, noisy airflow or slow warm-up often point to more than a heating capacity issue. In many commercial buildings, airflow issues stay hidden through summer and early fall, only becoming obvious once systems switch operating modes.


Heating season is shorter and generally less demanding than cooling in Arlington and Fort Worth, but it is far less forgiving of airflow and pressure imbalances.


Symptoms That Often Trace Back to Static Pressure

Heating-related complaints tied to static pressure usually show up in predictable ways:



  • Spaces that struggle to reach setpoint during morning warm-up
  • Uneven heating between zones on the same system
  • Supply air noise that appears only during heating calls
  • VAV boxes hunting or short cycling in mild winter conditions
  • BAS alarms related to airflow, fan speed or pressure rather than heat output


When these symptoms appear despite boilers, furnaces or heat exchangers operating normally, airflow resistance is often the underlying issue.


Why Heating Season Brings These Issues to the Surface

Heating mode changes how commercial HVAC systems move air. Those changes reduce tolerance for restrictions and control errors that cooling operation can mask.


Lower Airflow Exposes Restrictions

Most systems run lower airflow targets in heating than in cooling. When airflow drops, duct restrictions, dirty coils, undersized returns or poorly balanced zones consume a larger percentage of available static pressure. What passed unnoticed at higher cooling airflow suddenly limits delivery.


Fan Wear Shows Up at Reduced Speeds

Supply fans operating at lower RPM are less forgiving of mechanical issues. Worn belts, bearing degradation and wheel fouling can destabilize airflow when fans slow down. VFD-driven and ECM fans may hunt or fail to maintain pressure under these conditions, triggering comfort issues without obvious mechanical failure.


Return Air Problems Become Harder to Hide

In heating mode, reduced airflow leaves far less tolerance for return-side restrictions. Return paths that were marginal in cooling can create pressure imbalance once airflow drops, especially during morning warm-up. Interior offices and perimeter zones often show the first signs when return relief is undersized or poorly distributed.


Outside Air Damper Behavior Changes

During heating operation, outside air dampers typically remain at minimum positions for extended periods. Dampers that perform adequately during cooling modulation can struggle with accuracy at low positions, especially during morning warm-up. Even small positioning errors can disrupt return static pressure and destabilize airflow across the system.


Pressure Sensors and Control Logic Are Stressed

Static pressure sensors calibrated around cooling profiles may drift or misread conditions during heating. Control sequences also shift priorities between modes. Small inaccuracies that had little impact in summer can cause noticeable fan instability in winter.


Why Cooling Season Often Masks the Same Problems

Cooling operation provides more airflow and longer runtimes. Higher fan speeds overcome marginal restrictions, and continuous operation smooths out control instability. Comfort complaints during summer are often attributed to load or solar gain rather than airflow, allowing static pressure problems to persist unnoticed.


Heating season removes that margin.


Practical Solutions for Static Pressure Problems in Commercial Facilities

Verify Actual Static Pressure

Field measurements often reveal large gaps between design intent and real operation. Sensor accuracy and placement should be confirmed before adjusting setpoints.


Inspect Supply Fans and Drives

Belts, bearings, wheels and VFD response should be evaluated at heating speeds, not just cooling operation.


Assess Return Air Paths

Blocked or undersized returns are common contributors to static pressure imbalances. Door undercuts, transfer paths and return duct capacity all affect pressure balance.


Test Outside Air Dampers in Heating Mode

Observation in real operating conditions matters more than BAS commands. Actuator response and linkage condition should be verified.


Review Heating-Mode Control Sequences

Airflow logic and static pressure setpoints may need seasonal adjustment to match actual building behavior.


When Heating Complaints Point Beyond the HVAC Units

If tenant heating complaints sound like they could be attributable to static pressure imbalances, call Tom’s Commercial at (817) 857-7400. Our technicians can identify and correct problems to improve comfort, reliability and efficiency across every season.  


By Steve Roberts February 17, 2026
Aging heat exchangers can fail gradually before major breakdowns occur. Discover common warning signs Dallas–Fort Worth facility teams should monitor with Tom’s Commercial.
By Steve Roberts February 17, 2026
Misconfigured economizers can waste energy and impact indoor comfort. See how Dallas–Fort Worth commercial properties correct RTU setup issues with Tom’s Commercial.
By Steve Roberts February 17, 2026
Excessive reheat runtime increases energy costs and reduces efficiency. Learn what Dallas–Fort Worth facility teams should check in VAV systems with Tom’s Commercial.
By collin land January 21, 2026
Even after a fall tune-up, boilers can lose efficiency midseason. Learn what Dallas–Fort Worth facility managers should check to maintain performance with Tom’s Commercial.
By Steve Roberts January 19, 2026
Air leakage drives up heating costs and strain during cold spells. Learn how multistory Dallas–Fort Worth commercial buildings can reduce operational waste with Tom’s Commercial.
By Steve Roberts January 16, 2026
Heating complaints in mixed-use properties often stem from zoning, airflow, or load imbalances. See what Dallas–Fort Worth facility teams should evaluate with Tom’s Commercial.
By Steve Roberts January 14, 2026
Control sequence drift can quietly reduce heating performance during peak demand. Learn what Dallas–Fort Worth facility teams should monitor with Tom’s Commercial.
By Steve Roberts December 18, 2025
In modern low-load DFW buildings, oversizing drives short cycling, humidity issues, and demand spikes. Tom’s Commercial details right-sizing and controls fixes.
By Steve Roberts December 17, 2025
DFW properties: Tom’s Commercial covers acids, moisture, and particulates—testing, filtration, evacuation—so you prevent repeat compressor failures.
By Steve Roberts December 17, 2025
In Arlington, TX, Tom’s Commercial shows why VFD savings lag without updated sequences, setpoints, PID tuning, sensor QA, and recommissioning.